14 • Start Up

RI-215A

Operator’s Manual

Connecting the RI-215A to a Controller

Perform the following procedure to connect the RI-215A as a 3-wire 4 - 20 mA transmitter
to a controller.

1. Verify that power to the RI-215A has been turned OFF.

2. Connect one of the red wires from the RI-215A to the +24V transmitter terminal at the

controller.

3. Connect the other red wire to the - (DC ground) transmitter terminal at the controller.

4. Connect the yellow wire to the S or FB transmitter terminal at the controller.

Connecting the RI-215A to an External Alarm Device

CAUTION: The maximum current rating of the normally-open, dry contacts is 0.5 amp. If the

alarm device exceeds this rating, use the alarm contacts to control a relay with an
appropriate current rating.

1. Verify that power to the RI-215A has been turned OFF.

2. Connect the white wires to the external alarm. Refer to the wiring diagram in

Figure 3 on page 12.

3. If you do not connect the white wires to an alarm device, terminate these unused

wires.

Start Up

This section describes procedures to start up the RI-215A and place the RI-215A into
normal operation.

Introducing Power to the RI-215A

Complete all installation procedures described earlier in this chapter.

Verify that the wiring supplying power to the RI-215A has been connected correctly.

Turn on or plug in the incoming power at the power source.

Verify that the RI-215A shows a readout on its LCD as described in the next
subsection.

Warm Up

After you have turned on the power to the RI-215A, the unit takes about one minute to
begin operating. During this initial warm-up period, “CO2” is shown on the unit’s LCD.

After the initial warm up is completed, the gas sensor inside the RI-215A detects the
presence of CO

2

, and displays the concentrations of this gas on its LCD. Simultaneously,

the RI-215A also outputs a 4-to-20 mA signal (0 to 10 V optional) which corresponds to the
gas concentration.

CAUTION: Allow the RI-215A to warm up for an additional 30 minutes before continuing.