18 • Alarm Adjust Mode

RI-215A

Operator’s Manual

So if the alarm relay contacts are wired to turn on a ventilation system when the
concentration of CO

2

reaches the alarm point (e.g., 1000 ppm), the ventilation system will

remain on until the concentration of CO

2

falls to 50 ppm below the alarm point (e.g., 950).

Alarm Adjust Mode

Use the Up (

∆)

switch to enter Alarm Adjust Mode.

Verifying the Alarm Point

Three ranges of gas detection are available for the RI-215A: 0 - 2,000 ppm, 0 - 5,000 ppm,
and 0 - 9990 ppm. Detection ranges are set at the factory. When you ordered the RI-215A,
you should have specified one of these gas detection ranges for your unit.

The alarm point of the RI-215A is also set at the factory (e.g., 1000 ppm). To display the
current alarm point from the normal LCD, do the following:

1. Press and hold the Up (

∆)

switch. The alarm point appears (e.g., 10:00) on the LCD

(alarm verification screen). In this example, 10:00 indicates an alarm point of 1000
ppm. Note that the colon (:) will be flashing.

2. Release the Up (

∆)

switch to return to the normal LCD. Do not hold the (

∆)

switch for

more than three seconds or the unit will display the Alarm Adjust screen.

Further note that the RI-215A’s alarm relay has a built-in hysteresis (lag) of 50 ppm. After
the alarm point has been reached (e.g., 1000 ppm), the alarm relay will activate. As the
CO

2

concentration begins to fall, the alarm relay will deactivate 50 ppm below the

activation point (e.g., 950 ppm). The 50 ppm hysteresis keeps the alarm contacts from
“chattering” should the CO

2

concentration hover around the alarm point.

1000 ppm

950 ppm

Hysteresis

50 ppm

CO

2

Relay contact

Figure 6: Model RI-215A’s Built-in Hysteresis of 50 ppm

Closed

Open

Open