Model 1017-01 Operator’s Manual

• 5

Connecting the Sample Lines to the Model 1017-01

1.

Attach 1/4 inch O.D. rigid sample tubing to the INLET fitting.

CAUTION:

If you use flexible sample tubing (vinyl or polyurethane for example), use an
appropriate metal insert to seal the connection between the tubing and the INLET
fitting. See the Parts List for an example of an appropriate metal insert.

2.

Place the opposite end of the tubing at the sampling area.

CAUTION:

Avoid loops or slumps in the incoming sample line. To reduce response time, keep the
incoming sample line as short as possible.

3.

Install an appropriate line filter and flowmeter in a convenient location on the inlet
line. The 33-3050RK line filter with flow indicator is recommended for verifying there
is sufficient flow.

4.

Install an appropriate valve before the flowmeter to allow adjustment of the sample
flow to 1.0 LPM (a flowmeter with a built in valve may also be used).

5.

Attach 1/4 inch O.D. rigid sample tubing to the EXHAUST fitting.

6.

Route the opposite end of the tubing to an open area where the sample can safely
disperse.

Wiring the Model 1017-01

WARNING: Always verify that power is off before making or changing any wiring

connections.

1.

Verify that all power is off.

2.

Unscrew the cover from the housing.

3.

Install an appropriate conduit hub or cable bushing in the 3/4 NPT conduit opening
on the right side of the housing.

4.

Guide a six-conductor cable through the conduit opening on the right side of the
housing. See Table 2 below for the recommended cable wire sizes depending on the
distance between the Model 1017-01 and the controller.

5.

Connect the cable wires to the Model 1017-01’s sensor and input power terminal
strips as shown in Figure 4.

6.

Screw the cover back onto the housing.

7.

Route the cable back to the controller and the 24 VDC power source. Refer to the
controller instruction manual for sensor connections at the controller.

Table 2: Cable Size Recommendations

Distance From Controller

Recommended Cable size

Up to 1,200 meters

1.25 sq. CVV cable, 6 conductor

Up to 2,000 meters

2.0 sq. CVV cable, 6 conductor