35-3000RK-LEL Combustilbe Gas Sample-Draw Detector • 11

CAUTION:

If using shielded cable, leave the cable shield’s drain wire insulated and disconnected
at the sample-draw detector. You will connect the opposite end of the drain wire at

the controller.

7. Route the cable or wires in conduit leading from the sample-draw detector through

one of the conduit hubs at the controller.

CAUTION:

Do not route controller power wiring and detector wiring through the same hub.

The power cable may disrupt the transmission of the sensor signal to the controller.

8. Connect the wires to the applicable detector terminal strip and power terminals at the

controller as shown in Figure 4.

Figure 4: Wiring the Sample-Draw Detector to a Controller

Controller LEL

Sensor Terminals

Black

Green

Controller Terminals

Pump.,
Internally Wired

Combustible
Gas Sensor,
Internally Wired

Red

- (DC -)

+ 24 VDC

White

Red

Pressure Switch,
Internally Wired

Sample-Draw Detector
Main Circuit Board

A CTerminal

Strip Not Used

On This

Version

White

Green

Black

PUMP

115VAC

PSW

P- AMP

AMP

LEL/ O2

H

N GND

GND

LEL Sample-Draw Detector Housing

+

_

4/20

24V

RD WHT GRN BLK