14 • 35-3010RK-07 Sample-Draw Detector

Monthly

This procedure describes a test to verify that the sample draw detector responds properly
to the target gases.

Preparing for the response test

CAUTION:

This procedure may cause alarms at the monitoring device. Take appropriate action
to avoid this, such as entering the calibration mode at the monitoring device.

1.

Verify that the controller is reading 0 for the IR CH

4

and H

2

S channels and 20.9 for the

oxygen channel.

If the reading is not 0 for the IR CH

4

or H

2

S channels or 20.9 for the oxygen channel,

set the zero, or fresh air, reading as described in “Start Up” on page 12, then continue
this procedure.

2.

Assemble the calibration kit as described in the Calibration section of this manual.
Use of a 4-gas cylinder is recommended so that all channels may be checked at once.

Performing the response test

NOTE:

This procedure describes the RKI calibration kit that includes a demand flow
regulator.

1.

Screw the regulator into the calibration cylinder.

2.

Connect the calibration tubing from the regulator to the inlet line at or near the INLET
fitting. Gas will begin to flow.

3.

After approximately one minute, verify that the reading for each channel at the
controller stabilizes within ± 10% of the concentration of the test sample. If the
reading is not within ± 10% of the test sample, calibrate the sample draw detector as
described in the Calibration section of this manual.

4.

Remove the calibration tubing from the inlet line, then reconnect the inlet line.

5.

Store the calibration kit in a safe place.

Quarterly

Calibrate the sample draw detector as described in the “Calibration” section.

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the sample draw detector.

NOTE:

This troubleshooting guide describes sample draw detector problems only. See
the instruction manual for the controller if it exhibits any problems.

Fail Condition

Symptoms

The sample draw detector’s Fail light is on.

The controller is operating properly but indicates a reading well below zero on one or
more channels.