61-1000RK Combustible Gas Detector • 11

4.

After setting the response reading, turn the regulator’s on/off knob clockwise to close
it.

5.

Unscrew the regulator from the cylinder.

Returning to Normal Operation

1.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave regulator and calibration cup connected by the sample
tubing.

2.

When the controller display reading falls below the alarm points, return the controller
to normal operation.

NOTE

: If you do not allow the gas reading to decrease below the alarm points, then

unwanted alarms may occur.

3.

Verify that the controller display reading decreases and stabilizes at 0 %LEL.

4.

Store the components of the calibration kit in a safe and convenient place.

Parts List

Table 3 lists replacement parts and accessories for the 61-1000RK combustible gas detector.

Table 3: Parts List

Part Number

Description

18-0400RK-01

Junction box with spacers

61-0140RK

Replacement combustible gas detector

71-0067RK

61-1000RK Combustible Gas Detector Operator’s Manual (this document)

81-0007RK-01

Calibration cylinder (15% LEL Hexane in air, 34 liter)

81-0012RK-01

Calibration cylinder (50% LEL Methane in air, 34 liter)

81-0076RK-01

Zero air calibration cylinder (34 liter)

81-1003RK

Regulator, 0.5 liter/minute; continuous flow (for 17 and 34 liter calibration cylinders)

81-1117RK

Calibration cup