Installation, Mounting the combustible gas detector – RKI Instruments 61-1000RK User Manual

Page 7

Advertising
background image

61-1000RK Combustible Gas Detector • 3

detector into the hub. The terminal block within the junction box facilitates the wiring
process. A cover on the front of the junction box allows access to the interior of the
junction box.

Installation

This section describes procedures to mount the combustible gas detector in the
monitoring environment and wire the detector to a controller.

NOTE:

The 61-0140RK detector retains its explosion proof classification only when
installed in the explosion proof junction box. The detector is not explosion proof
if installed in a controller conduit hub.

Mounting the Combustible Gas Detector

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the detector is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.

Figure 2: Mounting the Combustible Gas Detector

J-Box

2.70

0.38

Combustible
Detector

3/4 x 1/2 Reducing
Bushing

.75

3/4 NPT
Female

3.65

7.50 max

Spacer, 3X

Advertising