61-1000RK Combustible Gas Detector • 1

Overview

This manual describes the 61-1000RK combustible gas detector (internal amplifier type).
This manual also describes how to install, start up, maintain, and calibrate the detector
when it is used with a gas monitoring controller. A parts list at the end of this manual
lists replacement parts and accessories for the combustible gas detector.

The 61-1000RK combustible gas detector includes the 61-0140RK combustible gas detector
and a junction box. This manual may also be used for the 61-0140RK combustible gas
detector which does not include a junction box and is normally mounted in one of a
controller’s conduit hubs. If you are using a 61-0140RK combustible gas detector,
disregard all references to the junction box and junction box terminal strip.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the combustible gas detector.

WARNING: When using the 61-1000RK, you must follow the instructions and warnings

in this manual to assure proper and safe operation of the 61-1000RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 61-1000RK as described in this manual.

Table 1: 61-1000RK Specifications

Target Gas

Combustible gas (Methane Calibration Standard)

Area Classification

Explosionproof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Detection Range

0 to 100% LEL

Response Time

90% in 45 seconds

Accuracy

± 5% of reading or ± 2% LEL (whichever is greater)