61-1001RK-05 Combustible Gas Detector• 1

Overview

This manual describes the 61-1001RK-05 hydrogen detector (internal amplifier type). This
manual also describes how to install, start up, maintain, and calibrate the detector when it
is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the hydrogen detector.

The 61-1001RK-05 hydrogen detector includes the NC-6205-05 hydrogen detector and a
junction box. This manual may also be used for the NC-6205-05 hydrogen detector which
does not include a junction box and is normally mounted in one of a controller’s conduit
hubs. If you are using a NC-6205-05 hydrogen detector, disregard all references to the
junction box and junction box terminal strip.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the hydrogen detector.

NOTE:

The following symbol on the detector label is a caution to the user to refer to this

documentation for installation instructions:

WARNING: When using the 61-1001RK-05, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the
61-1001RK-05 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 61-1001RK-05 as described in this
manual.

Table 1: 61-1001RK-05 Specifications

Description

Specifications

Target Gas

Hydrogen

Area Classification

Explosion proof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Detection Range

0 to 100 %LEL

Response Time

90% in 45 seconds

Accuracy

± 5% of reading or ± 2% LEL (whichever is greater)

!