65-2395RK-CH4 Methane Transmitter • 9

3.

Screw the regulator into the calibration cylinder.

4.

Screw the calibration cup onto the bottom of the detector.

5.

Use the sample tubing to connect the regulator to the calibration cup.

6.

Set a voltmeter to measure in the millivolt (mV) range.

7.

Plug the voltmeter leads into the test points on the amplifier. Plug the positive lead
into the red (+) test point; plug the negative lead into the black (-) test point.

8.

Use the following formula to determine the correct test points output for the test
sample.

Output (mV) = (calibrating sample/fullscale) X 400 + 100

For example, with a test sample of 50 %Vol. and a fullscale setting of 100 %Vol., the
correct output is 300 mV.

300 (mV) = (50/100) X 400 +100

Performing the response test

1.

Turn the regulator’s on/off knob counterclockwise to open the regulator. Gas will
begin to flow.

2.

Allow the gas to flow for one minute.

3.

Verify that the reading is within ± 20% of the response reading you determined earlier.

NOTE:

If the reading is not within ± 20% of the correct response reading, calibrate the
transmitter as described in “Calibration” on page 13 of this manual.

4.

Turn the regulator’s on/off knob clockwise to close the regulator.

5.

Unscrew the regulator from the calibration cylinder.

6.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave the regulator and calibration cup connected by the
sample tubing.

7.

Remove the voltmeter leads from the amplifier test points.

8.

Reinstall the junction box cover.

9.

When the controller display reading falls below the alarm setpoints, return the
controller to normal operation.

10. Store the components of the calibration kit in a safe place.

Biannually

Calibrate the methane transmitter as described in “Calibration” on page 13 of this manual.

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the methane transmitter.

NOTE:

This troubleshooting guide describes transmitter problems only. See the
controller operator’s manual for problems you may encounter with the
controller.