12 • 65-2395RK-CH4 Methane Transmitter

NOTE:

When a transmitter is first powered up with a new amplifier, the initial output
may be either high or below zero depending on the setting of the zero pot. Be
sure to make arrangements so that this does not cause unwanted alarms.

10. Turn on power to the controller.

11. Turn on the controller and place it into normal operation.

NOTE:

When first powered up, the transmitter will enter about a one minute period
when the 4-20 mA output is stabilizing and may be above the controller alarm
points or well below zero momentarily. RKI controllers have a one minute
warmup period when the controller does not display any gas reading or give any
alarm indication. The methane transmitter’s 4-20 mA signal should be stable by
the time the controller’s warmup period is over.

12. Allow the transmitter to warm-up for 5 minutes.

13. Calibrate the transmitter as described in “Calibration” on page 13 of this manual.

Table 4:Reconnecting the Amplifier

to the Controller

Amplifier Controller

Terminal Strip

Controller

Transmitter Terminal

Strip (typical)

PWR/SIG “-”

- (DC -)

PWR/SIG “S”

S (4 - 20 mA In)

PWR/SIG “+”

+ 24V

Table 5:Reconnecting the

Detector to the Amplifier

Amplifier Detector

Terminal Strip

Detector Lead

DETECTOR “R”

RED

DETECTOR “W”

WHT

DETECTOR “G”

GREEN

DETECTOR “B”

BLK