J-box h2s detector – RKI Instruments 65-2427RKSS-05 User Manual
Page 9
Advertising
![background image](/manuals/571489/9/background.png)
65-2427RKSS-05 H
2
S Detector • 5
Figure 3: Outline & Mounting Dimensions
2.
At the monitoring site you select, hang or mount the junction box with the detector
facing down (see Figure 3).
Wiring the H
2
S Detector to a Controller
WARNING: Always verify that the power source is OFF before you make wiring
connections.
1.
Turn off the controller.
2.
Turn off or unplug power to the controller.
3.
Remove the junction box cover.
WARNING: To maintain the explosion proof classification of the H
2
S detector, a
conduit seal must be used within 18 inches of the junction box conduit hub
used for wiring to the controller.
Text Oriented
This Way
2.40
3/4 NPT
Female,
2X
.20 Dia. x .45
Slot, 2X
3.66
3.15
8.00 max
J-Box
H2S Detector
3.34
1.10