65-2494RK/65-2497RK Oxygen Detector • 1

Overview

This manual describes the 65-2497RK oxygen detector. This manual also describes how to
install, start up, maintain, and calibrate the oxygen detector when used with a gas
monitoring controller. A parts list at the end of this manual lists replacement parts and
accessories for the oxygen detector.

The 65-2497RK oxygen detector includes the 65-2494RK oxygen detector and a junction
box. This manual may also be used for the 65-2494RK oxygen detector which does not
include a junction box and is normally mounted in one of a controller’s conduit hubs. If
you are using a 65-2494RK oxygen detector, disregard all references to the junction box
and junction box terminal strip.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the 65-2494RK and 65-2497RK oxygen detectors.

WARNING: When using the 65-2494RK/65-2497RK, you must follow the instructions

and warnings in this manual to assure proper and safe operation of the
65-2494RK/65-2497RK and to minimize the risk of personal injury. Be sure
to maintain and periodically calibrate the 65-2494RK/65-2497RK as
described in this manual.

Table 1: Specifications

Target Gas

Oxygen (O

2

)

Sampling Method

Diffusion

Detection Range

0-25% oxygen

Response Time

90% in 30 seconds

Accuracy

± 0.5% O

2

Operating Temperature

-4°F to 113°F (-20°C to 45°C)