65-2494RK/65-2497RK Oxygen Detector • 5

technique for the environmental rating of the junction box. The junction box is rated
NEMA 4X.

6.

Connect the two wires to the detector using the terminal block.

CAUTION:

If using shielded cable, leave the drain wire insulated and disconnected at the
detector. You will connect the opposite end of the cable’s drain wire at the controller.

7.

Secure the junction box cover to the junction box.

8.

Route the cable or wires leading from the oxygen detector through one of the conduit
hubs at the controller housing. Use appropriate conduit fittings and construction
technique for the environmental rating of the controller. RKI controllers are typically
rated NEMA 4X.

CAUTION:

Do not route power and detector wiring through the same conduit hub. The power
cable may disrupt the transmission of the detector signal to the controller.

9.

Connect the wires to the applicable controller terminal strip. See the controller
operator’s manual and the controller’s detector head specification sheet for the
65-2497RK detector.

Figure 4: Wiring the Oxygen Detector to a Controller

10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at

the controller. RKI controllers typically have a ground stud that is a convenient
grounding location.

Green

Oxygen detector assembly

J-Box

Controller Oxygen

Detector Terminals

White (+)

Green (-)

Shielded Cable

Controller Housing

White