RKI Instruments 65-2649RK-HC-04 User Manual

Page 43

Advertising
background image

65-2649RK-HC-04 M2A Transmitter Operator’s Manual

38

Adding an M2A to an Existing M2 Modbus Installation with Alternate Wiring

An M2A can be wired into an existing M2 Modbus system. The shape of the terminal PCB
will be different but the wiring connections are identical and the ground jumper on the
M2A must still remain installed.

Termination Jumper

The M2A includes a 2-pin termination header (see Figure 2) that is used when the M2A is
used in a Modbus system. Every M2A is supplied with a termination jumper (a jumper
block) installed onto this header. If the M2A is not used in a Modbus system, this jumper
has no function. When the M2A is installed in a Modbus system, this jumper must be
installed in an M2A that is at the end of a Modbus line. Any M2A in a Modbus system that
is not at the end of a line must have the termination jumper removed (see Figure 10 &
Figure 11 below).

Figure 10: Multiple M2As in a Daisy Chain Configuration

Figure 11: Multiple M2As in a Two Branch Configuration

Modbus

Master

Up to 128 M2As can be connected without a repeater

RS-485

RS-485

ID = 126

ID = 127

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Installed

ID = 125

ID = 1

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

ID = 128

RS-485

M2A

Termination

Jumper

Installed

Modbus

Master

Up to 128 M2As can be connected without a repeater

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

M2A

Termination

Jumper

Not Installed

ID = 2

ID = 3

RS-485

ID = 1

M2A

Termination

Jumper

Installed

ID = 127

ID = 4

Advertising