7 Maintenance
7-2. Regular maintenance mode
- 57 -
RM-5000
<Environmental Setting 1 "2-5">
In the environmental setting 1, specify the operation setting.
<<Environmental Setting 1>>
During maintenance
During inhibit
Lamp on
Lamp off
Lamp blinking
2-5. SETTING1
Press SET key.
SE 0. INHIBIT
Set Inhibit.
Press the ▲ or ▼ key to select
either ON/OFF, and then press the
SET key to confirm the selection.
When ON is selected, the
character I is displayed on the
LCD. As a result, an alarm is not
triggered to external circuits even
though the indicator/alarm unit is
in the detection mode.
SE 1. ALM P
Set the alarm setpoint value.
Alarm setpoint value setting
=> P58
SE 2. ALM DLY
Set the alarm delay time.
Press the ▲ or ▼ key to
change the value (second),
and then press the SET key
to confirm the value.
SE 3. F TEST
Perform a fault alarm test.
Fault Alarm Test
=> P58
To SE 0.INHIBIT Setting