RKI Instruments RM-5000 Series Indicator/Alarm Unit User Manual
Page 65

7 Maintenance
7-2. Regular maintenance mode
- 65 -
RM-5000
SE 3. GAS SEL
Select and set the gas name of
measured gas and the full scale.
Press the ▲ or ▼ key to make a
selection, and then press the SET key
to confirm the selection.
SE 4. PEAKHOLD
Select either ON/OFF of
holding the maximum
concentration value when a
gas is detected.
Press the ▲ or ▼ key to
select either ON/OFF, and
then press the SET key to
confirm the selection.
SE 5. ALM1 LCD
Select the LCD color (orange or
red) when the first alarm is
triggered.
Press the ▲ or ▼ key to select
a color, and then press the SET
key to confirm the selection.
Setting of the gas name of measured
gas and the full scale.
=> P71
SE 6. ALM BAR
Press the ▲ or ▼ key to
select either the display or
non-display of the alarm
setpoint value (bar).