Analog outputs setup – SATEC PM175 Manual User Manual

Page 51

Advertising
background image

‎Chapter 3 Display Operations

Menu Operations

Series PM175 Powermeters

51

Analog Outputs Setup

This entry appears only if the meter is ordered with optional
analog outputs. For more information on configuring analog
inputs in your meter, see

Programming Analog Outputs

in

Chapter 4.

To enter the menu, select the “A.Ou.1” or “A.Ou.2” entry from
the Main menu for the AO1 and AO2 output respectively, and

then press the ENTER button.

To change the analog output options:

1. Use the UP and DOWN arrow buttons to scroll to the

desired parameter.

2. Press the SELECT button to activate the lower window.
3. Use the UP and DOWN arrow buttons to adjust the

parameter value.

4. Press ENTER to confirm the new parameter setting, or

press ESC to discard changes.

5. You are returned to the middle window to select another

parameter, or store your new settings and exit the menu.


To store new settings and exit the menu:
1. When the middle window is highlighted, press the ENTER

button.

2. You return to the Main menu.

To exit the menu without saving your changes, press ESC.

The following table lists available analog output options. For a

list of the available output parameters and their scales, see

Programming Analog Outputs

in Chapter 4.

Label

Parameter Options

Description

OutP

Output
parameter

See Appendix B

Selects the measured parameter to
be transmitted through the analog

output channel.

Lo

Zero scale

Low engineering scale (in primary
units) for the analog output

corresponding to a lowest (zero)
output current (0 or 4 mA)

Hi

Full scale

High engineering scale (in primary

units) for the analog output
corresponding to a highest output

current (1 or 20 mA)

A.Ou.1

ESC

A.Ou.1

rt.U1

OutP

A.Ou.1

0

Lo

A.Ou.1

230

Hi