‎Chapter 4 PAS Application Software

General Meter Setup

70

Series PM175 Powermeters

The available relay options are shown in the following table:

Parameter

Options

Default

Description

Operation
mode

UNLATHCED
LATCHED

PULSE

KYZ

UNLATCHED

Unlatched mode: the relay goes into its
active state when the control setpoint is

in active (operated) state, and returns

into its non-active state when the
setpoint is released.
Latched mode: the relay goes into its
active state when the control setpoint

goes into active state and remains in
the active state until it is returned into

its non-active state by a remote
command.
Pulse mode: the relay goes into its
active state for the specified time, goes
into non-active state for the specified

time and remains in the non-active
state.
KYZ mode: the relay generates
transition pulses. The relay output state
is changed upon each command and

remains in this state until the next
command.

Polarity

NORMAL

(N.O.)
INVERTING
(N.C.)

NORMAL

With normal polarity, the relay is

normally de-energized in its non-active
state and is energized in its active

(operated) state.
With inverting polarity, the relay is
normally energized in its non-active

state and is de-energized in its active
(operated) state. It is called failsafe

relay operation.