Schwank ecoSchwank-X User Manual

Page 12

Advertising
background image

ECO-X / IL-X Manual
IM100117
RD: JAN 2013
RL: 05D - BA

12

SUSPENDED HORIZONTALLY: (long axis level)

TABLE 2: SUGGESTED LAYOUT / MOUNTING DISTANCES FOR COMFORT*

MODEL

TYPICAL

ABOVE
FLOOR

< X >

TYPICAL

BETWEEN

HEATERS

< Y >

TYPICAL

BETWEEN

ROWS

< Z >

ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75

ecoSchwank-X 26 - IL-X 100

12’ (366 cm)
15' (460 cm)
16' (490 cm)
19' (580 cm)
22' (670 cm)

18' (550 cm)
22' (675 cm)
28' (850 cm)
34' (1040 cm)

40’ (1220 cm)

25' (760 cm)
30' (910 cm)
40' (1220 cm)
60' (1830 cm)

80’ (2440 cm)

FIGURE 3: SUGGESTED LAYOUT FOR COMFORT

* The Mounting distances are suggested, and may vary depending on insulation/heat loss val-

ues, air movement/change, and other site conditions and comfort requirements. If in doubt,
please contact Schwank Design Services.

For ‘spot’ heating, the distance above the floor can be reduced by 2 to 4 feet (61 to 132 cm)

depending upon site conditions.

Y

X

X

Z

X

Z

SUSPENDED AT AN ANGLE 30° ON SHORT AXIS: (long axis level)

Long axis always level

Short axis may
rotate up to 30°

TYPICAL

ABOVE
FLOOR

< X >

TYPICAL

BETWEEN

HEATERS

< Y >

TYPICAL

BETWEEN

ROWS

< Z >

12’ (366 cm)
14' (430 cm)
15' (460 cm)
18' (550 cm)
20' (610 cm)

18' (550 cm)
22' (675 cm)
28' (850 cm)
34' (1040 cm)

40’ (1220 cm)

25' (760 cm)
30' (910 cm)
40' (1220 cm)
60' (1830 cm)

80’ (2440 cm)

MODEL

ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75

ecoSchwank-X 26 - IL-X 100