ECO-X 36-52 / IL-X 150-200 Manual
IM100116
RD: MAY 2009
RL: 05A - BA

26

IS THERE VOLTAGE FROM IGNITION
CONTROL TO COMBINATION GAS
VALVE?

CHECK ELECTRICAL WIRES FROM IGNITION

CONTROL TO COMBINATION GAS VALVE

CHECK IGNITION CONTROL, REPLACE IF

NECESSARY

NO

IS GAS COMING THROUGH
ORIFICE ON THE HEATER?

YES

ENSURE ALL GAS VALVES ARE OPEN

NO

YES

DOES THE IGNITION CONTROL
TERMINATE THE SPARKING
PROCESS AFTER THE HEATER IS
OPERATING?

CHECK SPARK IGNITER FOR CRACKS,

REPLACE SPARK IGNITER IF NECESSARY
→ENSURE THE SENSING WIRE IS SECURELY
CONNECTED TO THE SENSING PROBE
→CLEAN THE SENSING PROBE ON THE SPARK
IGNITER
→ENSURE THE FLAME SENSOR IS WITHIN 1/4"

ABOVE THE CERAMIC TILE

→CHECK FLAME SIGNAL WITH METER, IF LOW
CHANGE

SENSOR

→REPLACE WITH NEW IGNITION CONTROL
UNIT IF OTHER CHECKS ARE OK

DOES HEATER SHUT DOWN

AFTER IGNITION CEASES?

→CHECK FLAME SIGNAL USING A METER
INSTALLED IN SERIES WITH SENSOR CABLE,
CHECK (MICROAMPS) STRENGTH OF SIGNAL
FOR 1.5uA MINIMUM

YES

YES

NO

NO

STILL HAVING TROUBLE

OPERATING THE HEATER?

→REPEAT THE ABOVE TROUBLE SHOOTING
PROCEDURES
→IF THE PROBLEM PERSISTS, CONTACT YOUR
SCHWANK DISTRIBUTOR.

YES

NO

TROUBLESHOOTING
COMPLETE

→IF SIGNAL IS LOW REPLACE SENSOR AND
WIRE