Schwank ecoSchwank-X 52 User Manual

Page 7

Advertising
background image

7

ECO-X 36-52 / IL-X 150-200 Manual

IM100116

RD: MAY 2009

RL: 05A - BA

SUSPENDED

AT 30°

Max.

Stack

Height:

H’ = T - C

MOUNTING CLEARANCE TO COMBUSTIBLES

SUSPENDED HORIZONTALLY: Measured from outer surface of heater

MODEL

BELOW

< C >

Inches [cm]

SIDES

< S >

Inches [cm]

TOP

< A >

Inches [cm]

ENDS

< E >

Inches [cm]

ecoSchwank-X 36 - IL-X 150
ecoSchwank-X 52 - IL-X 200

121" [307]

121" [307]

55” [140]
55” [140]

52" [132]
52" [132]

39" [99]
39" [99]

FIGURE 1: MINIMUM DISTANCES TO COMBUSTIBLES - refer to

Table 1 for values

SUSPENDED AT AN ANGLE OF 30° *: Measured from outer surface of heater

NOTE: FOR AREAS USED TO STORE COMBUSTIBLE MATERIAL A ‘PEEL & STICK’ SIGN

IS SUPPLIED:

USE INDELIBLE MARKER TO RECORD VALUES ‘H’, ‘S’, ‘F’, & ‘B’.

POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A PROMINENT

LOCATION.

See next page for details.

C

SUSPENDED
HORIZONTALLY

C

A

F

B

TABLE 1: MINIMUM CLEARANCE TO COMBUSTIBLES

BELOW

< C >

Inches [cm]

FRONT

< F >

Inches [cm]

BACK

< B >

Inches [cm]

TOP

< A >

Inches [cm]

ENDS

< E >

Inches [cm]

121" [307]
121" [307]

84" [213]

84" [213]

55” [140]
55” [140]

52" [132]
52" [132]

39" [99]
39" [99]

MODEL

ecoSchwank-X 36 - IL-X 150
ecoSchwank-X 52 - IL-X 200

* NOTE

: Suspended between horizontal and 30°: Use the largest clearance from each column

~ See additional notes on previous & next pages ~

A

Site distance

to floor = T

Site distance

to floor = T

Max.

Stack

Height:

H’ = T - C

S

S

Advertising