11. HIGH ALTITUDE INSTALLATIONS

Canada:

all of our Luminous heaters are approved for altitudes zero to 2000 ft above sea level, or

2000 ft to 4500 ft above sea level and must be ordered as such, for either High or Low altitude.

USA:

if a heater is to be installed at altitudes above 2000 ft, the input must be reduced by 4% per

1000 ft and the orifice must be changed. (Contact your local distributor for further technical informa-
tion).