CHECK FOR PROPER TEMPERATURE
CONTROLLER OPERATIONS

•

REMOVE VALVE LEAD AT IGNITION

CONTROL, IF VALVE CLOSES, RECHECK
TEMPERATURE CONTROLLER AND WIR
ING, IF NOT, REPLACE GAS CONTROL.OR

CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF

YES

NO

MAIN BURNER LIGHTS

•

CHECK FOR 25 VAC ACROSS VALVE AND
VALVE TERMINALS IN IGNITER AND CAP, IF
NO VOLTAGE, REPLACE IGNITION CON-
TROL

•

SPARK IGNITER MAY BE OUT OF POSITION

CHECK ELECTRICAL CONNECTION BE
TWEEN IGNITION CONTROL AND GAS CON
TROL, IF OKAY, REPLACE GAS CONTROL

YES

NO

SPARK STOPS WHEN
BURNER LIGHTS

SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS

YES

NO

YES

NO

•

NOTE: IF IGNITION CONTROL GOES INTO
LOCKOUT, RESET SYSTEM

•

CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE

•

CHECK THAT BURNER FLAME COVERS
ALL ELECTRODES

•

IF CHECKS ARE OKAY, REPLACE IGNITION
CONTROL

•

NOTE: IF IGNITION CONTROL GOES INTO

LOCKOUT, RESET SYSTEM

•

CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE

•

NOTE: IF GROUND IS POOR OR ERRATIC,

SHUTDOWNS MAY OCCUR OCCASIONALLY,
EVEN THOUGH OPERATION IS NORMAL AT
THE TIME OF CHECKOUT IF CHECKS ARE
OKAY, REPACE IGNITION CONTROL

TROUBLESHOOTING ENDS