SP-MSTR-AU-05A

STR Manual

RD: NOV, 2003

RL: 5

KH

5. SYSTEMS INCORPORATING 90

O

BENDS AND 180

O

ELBOWS

Page 4

The STR Series radiant tube heater can be
installed in configurations as illustrated in
FIG: 2 (below) with a maximum of two 90

o

or one 180

o

elbow per heater. The use of

radiant elbows reduces the total maximum
vent allowable. See SECTION 9 (page 11):
Flue Venting.

Both the 90

o

and 180

o

elbows are shipped as

a kit with two end-plate hangers to close off
the reflector ends each side of the elbow (s).
The reflector must be secured with four
screws to each of the end-plate-hangers.
SEE FIG: 3 (PAGE 5) and FIG: 6 (PAGE 6).

FIGURE 2 SYSTEM CONFIGURATIONS

System Configuration
1 Straight line
2 “U” tube with 180-degree elbow kit
3 “L” tube with 90-degree elbow kit
4 Twinned tubes into common TEE flue

vent

Venting Options
A Flue vent through wall 4”
B Flue vent through wall or roof 6”
C Flue vent through roof
D Flue vent into building, exhaust fan

interlocked with heater

E Combustion air intake from outside

through wall

F Combustion air intake from outside

through roof

G Combustion air intake from inside
building

IMPORTANT: On STR 60 and 45 models, a minimum of 10’ of straight

radiant tube must be connected to the burner before any
elbow.