Connecting to a infant/patient monitoring system, De 101-kde, Remote rex remote reset – SDC 101-DE/101-KDE Delayed Egress Controller User Manual
Page 11: Patient monitor

101-DE
101-KDE
PWR LOCK RED R
NO C
TRIG REX
RESET
C NO
C NO
C NO
- +
- +
Trigger
Switch
-
+
3
45
67
8
To
Power
Supply
REMOTE
REX
REMOTE
RESET
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
Standard Exit
Device
No switch
No Power Transfer
TO FIRE COMMAND
CENTER
115 VAC
Door With Latch Assembly
Activation By Door Movement
Power Supply
TO PATIENT MONITORING
SYSTEM
PATIENT
MONITOR
Connecting to a Infant/Patient Monitoring System
Wire the remote reset terminals to the alarm contacts of the patient monitoring system. To keep the door
normally unlocked, Close and hold the Remote Rex input . A contact closure from the patient monitoring
system cause the 101-DE/101-KDE will immediately relock the door. Egress is still possible through the normal
15 second delay on egress process. When the contact closure is released, the system will return to the
unlocked condition.
P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd Rev B10 04-13 Page 11
Connection to a Infant/Patient Monitoring
System has not been investigated by UL.