24-2

SCADA 3000 User’s Manual

Figure 1: Module Mounting Dimensions

Power Supply and Grounding

The Pulse Count Module operates on 10–15VDC. Typically the module is powered from

the AUX PWR terminals on the SCADA 3000 main unit. This is preferred because the AUX

PWR from the main unit is battery-backed in the event of a power failure, when a battery

is connected to the main unit. Alternately, you may connect the module to any 10–15VDC

power source. The module requires 1.5 Watts of power.

Figure 2: Pulse Count Module connected to SCADA 3000