ARI* CAPACITY RATINGS
542J150,180 UNITS
LEGEND
*Air-Conditioning and Refrigeration Institute.
NOTES:
542J units are rated in accordance with ARI Standard 340.
Cooling ratings are net values, reflecting the effects of circulating fan
heat. Ratings are based on:
ESP: –.35 in. wg
Cooling Standard: 80 F db, 67 wb indoor coil entering-air temperature
and 95 F outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 47 F db, 43 F wb outdoor coil entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 17 F db, 15 F wb outdoor coil entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
PHYSICAL DATA
UNIT
542J
COOLING
HEATING-HIGH TEMP
HEATING-LOW TEMP
SOUND
RATING
(decibels)
Total
kW
Net
Capacity
(Btuh)
Cfm
IPLV
EER
Total
Capacity
(Btuh)
Total
kW
COP
Total
Capacity
(Btuh)
Total
kW
COP
150
14.3
140,000
4500
12.4
9.8
136,000
12.4
3.2
72,000
10.0
2.1
87
180
18.5
172,000
5200
9.7
9.3
172,000
15.3
3.3
90,000
12.5
2.2
88
COP — Coefficient of Performance
db
— Dry Bulb
EER — Energy Efficiency Ratio
ESP — External Static Pressure
IPLV — Integrated Part-Load Value
kW
— Kilowatts
wb
— Wet Bulb
WEIGHT DISTRIBUTION AND CENTER OF GRAVITY
UNIT
542J
WEIGHT
WEIGHT OF CORNER
DIMENSIONS
Lb
Kg
A
B
C
D
X
Y
Z
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
ft-in.
mm
ft-in.
mm
ft-in.
mm
150
1615
733
366
166
356
161
360
163
534
242
3
′-1″
947
3
′-2″
965
1
′-10″
559
180
1925
874
464
211
496
225
477
217
487
221
3
′-6″
1059
3
′-8″
1105
1
′-10″
559
5
0
T
F
Q0
04-
01
2
54
2J1
50,
1
8
0