ARI* CAPACITY RATINGS

542J150,180 UNITS

LEGEND

*Air-Conditioning and Refrigeration Institute.

NOTES:

542J units are rated in accordance with ARI Standard 340.

Cooling ratings are net values, reflecting the effects of circulating fan
heat. Ratings are based on:
ESP: –.35 in. wg

Cooling Standard: 80 F db, 67 wb indoor coil entering-air temperature
and 95 F outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 47 F db, 43 F wb outdoor coil entering-air temperature.

Low-Temp Heating Standard: 70 F db indoor coil entering-air temper-
ature and 17 F db, 15 F wb outdoor coil entering-air temperature.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.

PHYSICAL DATA

UNIT

542J

COOLING

HEATING-HIGH TEMP

HEATING-LOW TEMP

SOUND

RATING

(decibels)

Total

kW

Net

Capacity

(Btuh)

Cfm

IPLV

EER

Total

Capacity

(Btuh)

Total

kW

COP

Total

Capacity

(Btuh)

Total

kW

COP

150

14.3

140,000

4500

12.4

9.8

136,000

12.4

3.2

72,000

10.0

2.1

87

180

18.5

172,000

5200

9.7

9.3

172,000

15.3

3.3

90,000

12.5

2.2

88

COP — Coefficient of Performance
db

Dry Bulb

EER — Energy Efficiency Ratio
ESP — External Static Pressure
IPLV — Integrated Part-Load Value
kW

Kilowatts

wb

Wet Bulb

WEIGHT DISTRIBUTION AND CENTER OF GRAVITY

UNIT

542J

WEIGHT

WEIGHT OF CORNER

DIMENSIONS

Lb

Kg

A

B

C

D

X

Y

Z

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

ft-in.

mm

ft-in.

mm

ft-in.

mm

150

1615

733

366

166

356

161

360

163

534

242

3

′-1″

947

3

′-2″

965

1

′-10″

559

180

1925

874

464

211

496

225

477

217

487

221

3

′-6″

1059

3

′-8″

1105

1

′-10″

559

5

0

T

F

Q0

04-

01

2

54

2J1

50,

1

8

0