Bryant 548F User Manual

Page 18

Advertising
background image

18

MODEL NUMBER NOMENCLATURE — 548F UNITS

(ODS Model Number)

ARI* CAPACITY RATINGS

548F036-060

548F072-120

LEGEND

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 60,000 Btuh or less.

**The IPLV applies only to 2-stage heat pump units.

††Not ASHRAE 90.1-99 compliant.

NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.

3. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db
air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db out-
door entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F
db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F
db, 15 F wb outdoor entering-air temperature.

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High Temp)

SOUND

RATING

(decibels)

Capacity

(Btuh)

SEER†

Capacity

(Btuh)

HSPF

Belt

Drive

Direct

Drive

036

3

35,600

10.20

10.00

34,400

6.7

84

048

4

46,500

10.00

9.70

46,500

7.0

80

060

5

57,000

10.00

9.90

57,000

7.5

82

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High)

HEATING

(Low)

IPLV**

SOUND

RATING

(decibels)

Capacity

(Btuh)

EER

Capacity

(Btuh)

COP

Capacity

(Btuh)

COP

072††

6

70,000

9.05

72,400

3.20

42,000

2.14

—

82

090††

7

1

/

2

86,000

9.00

78,000

3.00

39,000

1.80

9.3

86

102††

8

1

/

2

96,000

8.90

96,000

3.00

55,000

2.00

8.85

86

120††

10

112,000

9.00

105,000

3.10

59,000

2.00

9.0

84

COP

—

Coefficient of Performance

db

—

dry bulb

EER

—

Energy Efficiency Ratio

HSPF

—

Heating Seasonal Performance Factor

IPLV

—

Integrated Part-Load Values

SEER

—

Seasonal Energy Efficiency Ratio

wb

—

wet bulb

Voltage Designation
E –
460-3-60
J – 208/230-1-60†
P – 208/230-3-60
T – 575-3-60

548F E X 090 000 AA

548F – Single-Package

Heat Pump
Unit

X – No Heat Installed.

(Field-installed electric heaters available.)

Factory-Installed Options*

Nominal Tons
036 –
3

090 – 7-1/2

048 – 4

102 – 8-1/2

060 – 5

120 – 10

072 – 6

Electric Heaters
000 –
No factory-installed electric heaters

LEGEND

*Refer to Trade Price Sheets or contact your local representative for specific

information regarding which options are available on which units.

†Single-phase is only available on 036-060 size units.

NOTE: The example model number 548FEX090000AA designates a 7

1

/

2

ton

460-3-60 volt electric heat pump unit with factory-installed economizer.

ODS

—

Order Distribution System

50

T

F

Q

0

04

-0

12

5

48F

036

-1

20

Advertising