TYPICAL WIRING SCHEMATIC (cont)

LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATIC

AHA

— Adjustable Heat Anticipator

BKR W/AT — Breaks with Amp Turns
C

— Contactor, Compressor

CAP

— Capacitor

CB

— Circuit Breaker

CC

— Cooling Compensator

CH

— Crankcase Heater

CLO

— Compressor Lockout

COMP

— Compressor Motor

CT

— Current Transformer

CTD

— Compressor Time Delay

DAT

— Discharge Air Thermistor

DB

— Defrost Board

DFT

— Defrost Thermostat

DM

— Damper Motor

DR

— Defrost Relay

DU

— Dummy Terminal

EC

— Enthalpy Control

EQUIP

— Equipment

FL

— Fuse Link

FPT

— Freeze Protection Thermostat

GND

— Ground

HC

— Heater Contactor

HPS

— High-Pressure Switch

HR

— Heat Relay

HTR

— Heater

IFC

— Indoor-Fan Contactor

IFCB

— Indoor-Fan Circuit Breaker

IFM

— Indoor Fan Motor

IP

— Internal Protector

L

— Light

LOR

— Lock Out Relay

LPS

— Low-Pressure Switch

LS

— Limit Switch

OAT

— Outdoor-Air Thermostat

OFC

— Outdoor-Fan Contactor

OFM

— Outdoor Fan Motor

OP

— Overcurrent Protector

PL

— Plug Assembly

QT

— Quadruple Terminal

RVR

— Reversing Valve Relay

RVS

— Reversing Valve Solenoid

TB

— Terminal Block

TC

— Thermostat Cooling

TH

— Thermostat Heating

TRAN — Transformer

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Factory Wiring

Field Wiring

Option/Accessory Wiring

To Indicate Common Potential Only:
Not To Represent Wiring

NOTES:

1. Compressor and/or fan motor(s) thermally protected. Three-phase motors are protected

against primary single phasing conditions.

2. If any of the original wire furnished must be replaced, it must be replaced with type 90° C

wire or its equivalent.

3. CB1,2 must trip amps are equal to or less than 156% FLA, IFCB 140%.
4. The CLO locks out the compressor to prevent short cycling on compressor overload and

safety devices. Before replacing CLO, check these devices.

5. Jumpers are omitted when unit is equipped with economizer.
6. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies

a single-pole, double-throw contact. An underlined number signifies a normally-closed
contact. Plain (no line) number signifies a normally-open contact.

7. Remove jumper between terminals RC and RH.