Sportsliter Solutions Two circuit remote ballast User Manual

Two circuit remote ballast

Advertising
background image

TWO CIRCUIT REMOTE BALLAST

INSTALLATION AND SERVICING INSTRUCTIONS

SLS0036 SLS 2 Remote Ballast Instruction-A 1/14

Wiring Instructions: (See Figures 2 & 3)

WARNING!

• Dangerous voltages exist within this product.
• This enclosure includes two electrical supply circuits. To reduce fire and shock hazards
disconnect power to both circuits before servicing.
• To reduce the risk of injury, operate and maintain to meet all applicable codes.
• Installation is to be performed by a qualified electrician only.
• Provide proper ground for all system components.
• Read and follow all instructions and labels before and during installation.
• Failure to properly install this product will void manufacturer’s warranty.
• Handle and secure so ballast enclosure cannot fall.
• Use protective equipment to avoid injury during installation of this heavy product.
• Do not route wiring through top of enclosure.

NOTE:

A complete system includes the ballast enclosure, lighting fixtures, wiring harness,

crossarms and poles.
This ballast enclosure should be installed at a minimum height of 10 feet (3 meters)

above grade.

Enclosure Installation:
(Figures 1, 2, & 3)

Important: Installation requires the use of a pole

equipped with mounting couplings and wireway. (

Figure 1)

1. Remove peel strip from gasket supplied in hardware bag.
2. Apply gasket to the back of enclosure around the 2-

1

2

”x4-

1

2

(63.5mmx114.3mm) hole. (

Figure 3)

3. Install bolt (2) and lockwasher (3) in the top coupling. (

Figure 2) Leave

1” (25.4mm) of thread exposed.
4. Position lift bracket (4) over the bolt (2) and lockwasher (3)

NOTE: The top of keyhole in bracket must contact the bolt to support

the 280 pound (127Kg) enclosure.
5. Align the wireway opening in the enclosure with the wireway opening in

the pole.

Do not damage gasket!

6. Install bolt, lockwasher and flatwasher through hole inside of enclosure

and into the coupling in pole.
7. Tighten both bolts to a minimum of 40ft/lbs.
8. Seal all openings between pole and enclosure.

Figure 1

Wiring and Electrical Instructions:
• The enclosure includes two electrical supply circuits.
• The enclosure voltage must match the supply voltage.
• Standard wiring is single phase.

Three phase requires a- “T” on the

catalog number. (Consult factory)
• Total operating amps for each supply circuit is shown on the electrical
datamarker located near each switch
• Enclosure are factory wired to operate as a separate unit. (Contact factory

multiple enclosures in series)
• Enclosure includes factory fusing of all branch circuits.
• Separate internal electrical switching is included for each circuit:

Thermal Magnetic Breaker is standard for 208v, 220v and 240v

Load Break Switch is standard for 277v, 347v and 480v

“-TB” indicates Thermal Magnetic Breaker for 277, 347v and 480v.

Drawing Number: 268-1220-9901

Installation Instructions