Steriflow Mark 15 Series User Manual

Page 2

Advertising
background image

Steriflow, a division of Jordan Valve
3170 Wasson Road • Cincinnati, OH 45209
513.533.5600 • 800.543.7311 • 513.871.0105 (f)
[email protected] • www.steriflowvalve.com

Steriflow Valve reserves the right to make revisions to its product, specifications, literature and related information without notice. Please visit our
website at www.steriflowvalve.com for the latest information on our products.

MK15/0910/5K/AB

M

ark

15 T

op

M

ounTed

p

neuMaTic

V

alVe

p

osiTioners

s

peciFications

Input:

3-15, 6-30, 3-9 or 9-15 psi (0,2-1,0; 0,4-2,1; 0,2-

0,6; or 0,6-1,0 bar )

Air Supply Pressure:

35 – 45 psi reverse acting 3-9 / 9-15 / 3-15 / 6-30

ranges

20 – 25 psi direct acting 3-9 / 9-15 / 3-15 ranges

35 – 45 psi direct acting 6-30

Output

: 0-100% supply pressure

Operating Temperature Limits:

-40°F to +180°F (-40°C

to + 82°C)

Air Consumption (@20 psi):

0.25 scfm; (@ 1,4 bar:

0.0007N/m3)

Flow Capacity:

4.4 scfm (0.125N/m3) (for 3-15 psi output

pressure change) (0,2-1,0 bar)

Repeatability:

1/2% of full stroke

Sensitivity:

responds to control air pressure changes as

small as 0.1% of full range

Connections:

1/4” FNPT

Dimensions:

4.65”H x 3.5” Diameter (117,6mm x

88,9mm); external dimensions when mounted

Net Weight:

2-1/2 pounds (1,1 Kg)

The topworks of the valve must have six, 1/4-20 x 9/16

deep holes (minimum) blind tapped, equally spaced on a

03,000 B.C. for mounting positioners.

D

imensions

3.5"

8.89cm

2.0"

5.08cm

4.625"

11.74cm

How to Order

1. See Mark 978 Control Valve model order grids

2. Select the appropriate base valve model. See mod-

els 978TP (TP for Top Mounted Positioner)

Advertising