Installation, General safety information, Installation checklist – Regency Hampton H35 Large Gas Stove User Manual

Page 9: Clearances to combustibles

Advertising
background image

Hampton® H35-2 Direct Vent Freestanding Gas Stove

9

INSTALLATION

GENERAL SAFETY

INFORMATION

1) The appliance installation must conform with

local Canadian Electrical Code.

2) The appliance when installed, must be electri-

cally grounded in accordance with local codes,
or in the absence of local codes with the cur-
rent National Electrical Code, ANSI/NFPA 70
or CSA C22.1 Canadian Electrical Code.

3) The appliance should be inspected for shipping

damage before use and serviced annually by
a professional service person
. More frequent
cleaning may be required due to excessive
lint from carpeting, bedding material, etc. It
is imperative that control compartments, and
circulating air passageways of the appliance
be kept clean and free from excessive lint from
carpeting.

4) See general construction and assembly in-

structions. The appliance and vent should be
enclosed when installed in or passing through
a living area, where children may come in
contact with it.

5) This appliance must be connected to the speci-

fi ed vent and termination cap to the outside
of the building envelope. N e v e r v e n t t o
another room or inside a building. Make sure
that the vent is fi tted as per the instructions
starting in the "Exterior Vent Terminal Loca-
tions" section.

6) Inspect the venting system annually for block-

age and any signs of deterioration.

7) Venting terminals shall not be recessed into a

wall or siding.

8) Any safety glass removed for servicing must

be replaced prior to operating the appliance.

9) To prevent injury, do not allow anyone who

is unfamiliar with the operation to use the
fi replace.

INSTALLATION

CHECKLIST

1) Locate your appliance. Refer to the following

sections:

a. Clearances to combustibles

b. Locating Your Gas Stove

c. For venting requirements, see "Venting
Introduction" to "Venting Arrangements"

Section.

2) Install Optional Fan. Refer to the "Optional Fan

Installation" section.

3) Set vent restrictors. Refer to the "Vent Restrictor

Position" section.

4) Install venting. Refer to the following sections

where applicable:

a. Check all venting requirements.
See "Venting Introduction" to "Venting

Arrangements" sections.

b. Vertical Termination with Co-linear Flex

System

c. DV Stove Horizontal Vent Kit

d. Dura-Vent Termination Kit.

5) Make gas connections. Refer to the "Gas

Connection" section

Test the pilot. Must be as per diagram in the
"Maintenance Instruction" section.

If converting to Propane, make changes prior
see the "Conversion from Natural Gas to
Propane" section.

6) Test Gas Pressure. Refer to the "Gas Pipe

Pressure Testing" section.

7) Install standard and optional features. Refer

to the following sections where applicable:

a. Brick Panels

b. Log Set Installation

c. Wall Thermostat

d. Remote Control

e. Optional Side Shelves

8) Final check. Refer to the "Final Check" section.

Before leaving this unit with the customer, the

installer must ensure that the appliance is fi r-
ing correctly and operation fully explained
to customer
.

This includes:

1) Clocking the appliance to ensure the correct

fi ring rate (rate noted on label) after burning
appliance for 15 minutes.

2) If required, adjusting the primary air to ensure

that the fl ame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.

CAUTION: Any alteration to the product that
causes sooting or carboning that results in
damage is not the responsibility of the manu-
facturer.

CLEARANCES TO

COMBUSTIBLES

The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector. The farthest distance is
correct if the two clearances do not coincide.

For example, if the appliance is set as indicated in
one of the fi gures but the connector is too close,
move the stove until the correct clearance to the
connector is obtained.

This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.

This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl.

Use the minimum clearances shown in the dia-
grams below:

H35-NG2 & H35-LP2 Clearances

A Side Wall to Unit

6-1/2" / 165 mm

B Back Wall to Unit

6" / 152 mm

C Vertical Vent Pipe to Back Wall

2" / 50 mm

E Unit Corner to Wall

2" / 50 mm

Unit Top to Alcove Ceiling 36" / 914 mm

Minimum ceiling height is 36" /914 mm from top

of unit.

Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.

Advertising