A major advantage of the G438 is its wide ranging capabilities and ease of configuration.

For example, in a valve positioning application a potentiometer is sometimes used as a feedback signal.

Quite often a wide open valve is only a 25% turn of the feedback potentiometer. In this case the G438 can

easily be adjusted with the zero and span to provide a full scale output signal (e.g. 4-20mA) representing

0-25% or even 50-75% of the potentiometer input.

Unless otherwise specified, the factory presets the Model G438 as follows:

Input Range: 0 to 100%

Output: 4 to 20mA

The DC power input accepts any DC source between 9 and 30V; typically a 12V or 24Vdc source is used.

For other output ranges, refer to Tables 1 and 2 to reconfigure switches SW1 and SW2 for the desired input

and output ranges.

Do not attempt to change any switch settings with power applied. Severe damage will result!

1. With power disconnected, set the output and input switch selectors (SW1 and SW2) to the desired

ranges (Tables 1 and 2).

2. Connect the input and output as shown in wiring diagram. Connect the output to the actual device load

(or a load approximately equivalent to the actual device load value) and apply power.

NOTE: To maximize thermal stability, final calibration should be performed in the operating installation,

allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.

3. Set the input potentiometer to the desired minimum and adjust the zero potentiometer for the desired

minimum output.

4. Set the input potentiometer to the desired maximum and adjust the span potentiometer for the desired

maximum output.

5. Repeat steps 3 and 4, if necessary, for best accuracy.

Configuration

WARNING

Calibration

INPUT

ZERO

SPAN

ULTRA

SLIMPAK

G438

Output (+)

Output (-)

DC Power (+)

52

21

11

12

22

41

51

42

DC Power (-)

_
_

Potentiometer Input

(full counter clockwise)

Potentiometer Input

(wiper)

Potentiometer Input
(full clockwise)

Shield Ground

52 51
42 41

12 11
22 21