Weidmuller WAVE Analog PRO DC User Manual
Page 10
Advertising
4.
Mounting
The analog signal isolators are mounted on standard TS 35 rails.
5.
Electrical connection
Warning!
Do not operate inputs for current and voltage simultaneously!
For applications with high isolation voltages, take measures to
prevent accidental contact and make sure that there is sufficient
distance or insulation between adjacent devices!
5.1 Power supply
22 to 230 V AC/DC ± 10 %, approx. 1 W, AC 48 to 62 Hz
Terminal assignments
1 Input +
> 5 mA
2 Input +
≤ 500 mV / ≤ 5 mA
3 Input +
> 500 mV
4 Input -
5 Output +
6 Output -
7 Power supply
8 Power supply
Wire cross-section max. 2.5 mm
2
Multi-wire connection max. 1 mm
2
(two wires with same cross-section)
5 6
7 8
3 4
1 2