Weidmuller WAVE Control: Current Monitoring Module User Manual

Page 3

Advertising
background image

13

12

1.

General instructions

The WAVECONTROL current-monitoring module should only be installed
by qualified personnel. Qualified personnel, as defined in these operating
instructions, are persons considered in 0105 Part 1/DIN EN 50110-1 as
electrically skilled workers or electrotechnically instructed personnel. The
signal conditioner should only be powered up following professional
installation.

Caution! • Electronics units must not be removed from their enclosure

when the voltage supply is connected

• The module must be disconnected from the voltage supply

when configuring the DIP switches on the printed-circuit board
(disconnect the connector from the module)

• Observe ESD regulations

Care must be taken to prevent a direct electrostatic discharge
when setting the DIP switches. Regulations of the county in
which the modules are to be operated are to be observed (for
example, Germany, VDE 0100) when selecting and installing
electrical wiring.

2.

Application

WAVECONTROL current-monitoring modules, measure DC, AC and non-
sinusoidal currents up to 60 A, and can be used for monitoring tasks in
diverse areas.
All variables are configured via DIP switches. Further calibration is not
necessary. The measurement circuit is galvanically isolated. Measurement
results are available for further processing as a relay contact or analog value.
All modules are available with pluggable screw or tension clamp connections.

3.

Mounting and Settings

3.1 Range adjustments

1. Remove

ቢ connector

2.

Press locking clips

ባ on both sides of the enclosure and pull out the

circuit board

3.

Make required adjustments to the input range, hysteresis, frequency
and relay control using the DIP switches (by print to the side of the
enclosure

ቤ).

4.

Replace connector after making adjustments
The connectors have been coded by the manufacturer, ensuring that
they cannot be reversed

ብ.

5.

If using the feed-through version, push through enclosing wire

Warning!!
The circuit board can only be inserted in one position.

3.2 Cross-connections for voltage supply

A maximum feed through of 2 A is possible
The cross-connectors have been coded by the manufacturer, preventing a
short circuit should the cross-connectors be reversed

405872_IS_WAVEcontrol.QXD 29.07.2002 11:53 Uhr Seite 12

Advertising