12
Switching the current output
Output
SW1
SW2
0...20 mA
0
0
4...20 mA
1
1
1 = on
0 = off
Selecting the output
Wiring diagram
Output
GND 1
U / I
0...10 V
9
7
0...20 mA
9
8
4...20 mA
9
8
Selecting the input
Wiring diagram
Input
0V
Vac
0...30 Vac
1
2
0...70 Vac
1
3
0...130 Vac
1
4
0...250 Vac
1
5
0...450 Vac
1
6