2 input calibration points – Weidmuller ITX+ - Universal signal isolator / amplifier User Manual

Page 24

Advertising
background image

2

Input Calibration points

Range

Values

Notes

Volts/Thermocouple

10 mV, 20 mV,
50 mV, 80 mV,
200 mV, 1 V

If the internal switches are set to 10 V, you must supply
a signal ten times the displayed value, e.g. 10 V for the
1V point.

mA

20 mA

RTD/Resistance

100 Ω, 200 Ω,
500 Ω, 800 Ω,
2 kΩ, 10 kΩ

Use four wire mode

Individual calibration

As selected

Allows you to recalibrate any of the points above

Fine adjust

Current input

Fine tune the adjustment for the range you have selected.

All

All ranges

Complete calibration of all points. Internal switches must
be in the 1V position.

Input calibration
1. Save the current calibration to disk (select ‘Save Calibration data’

from the ‘Device’ menu).

2. Select ‘Calibrate Input’ from the ‘Device’ menu.
. Enter the calibration password (Default is 101).
. Choose the calibration required (see Input calibration points table for

guidance).

5. Supply the signals requested by the software and follow the

instructions on screen. Press the ‘Done’ button when finished.