7. Set the input source to the maximum value required, e.g., 20 mA for

a 4-20 mA signal.

8. Adjust the output using the up and down keys until the output is

at the value required at maximum input, e.g., 20 mA for a 4-20 mA
output.

9. If you are happy with the results, press ENT twice. The ‘Ready

to save’ LED will switch on then turn off. After two seconds the
instrument will return to normal operation (with the Status LED set to
green). Otherwise press the ENT key and then the Up or Down key
to discard the calibration values.

Ready to Save

Status:
Green for Run
Red For Calibrate Mode

Output Calibration

ENT

DOWN

UP