Installation – Weidmuller wavePak - Configurable singal isolator-converter User Manual

Page 9

Advertising
background image

9

• Installation

General
These units must only be installed by qualified staff in accordance with
the information given in this manual and all relevant national electrical
wiring and safety rules must be followed.
Locate the instrument in an area that is free from dust, moisture and
corrosive gases. Do not cover the ventilation holes at the side of the
case.

Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).

Terminal

Signal

1

Supply +

Power Supply

7

Supply −

4

Voltage Input +

Voltage Input

Input Type Jumper to ‘Volts’
Field Supply Jumper to ‘Off’

3

Voltage Input −

2

Current Input +

Current Input

Input Type Jumper to ‘Current’
Field Supply Jumper to ‘Off’

3

Current Input −

3

Device +

Loop Powered Transmitter
Input

Input Type Jumper to ‘Current’
Field Supply Jumper to ‘On’

2

Device −

6

Voltage Output +

Voltage Outputs

Output Type jumper to ‘Volts’

5

Voltage Output −

8

Current Output +

Current Outputs

Output Type jumper to ‘Current’

5

Current Output −