Step 1: remove power from the drive, Step 2: remove the protective covers – Rockwell Automation 20P PowerFlex DC Drive - Frame A SCR Modules for Drive w/Power Traces Circuit Board User Manual
Page 3

PowerFlex® DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board
3
Step 1: Remove Power
from the Drive
1. Remove and lock-out all incoming power to the drive.
Step 2: Remove the
Protective Covers
1. Remove the two screws that secure the power terminal cover to the
drive and slide the cover down and off the drive chassis.
!
ATTENTION: Remove power before making or breaking cable
connections. When you remove or insert a cable connector with
power applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:
•
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
•
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
L1
L2
L3
O
I