Installation – Rockwell Automation 140G-Rx Installation Instruction-140G-R User Manual
Page 4

DIR 1000682R0002 (L5757)
(4)
Fig.7
Table of circuit-breaker weights (kg)
Note
The weights given in the table refer to circuit-breakers complete with LSIG releases and relative current sensors, excluding the accessories.
4. Installation
4.1 Installation conditions
Install the circuit-breaker in a dry, dust-free, non-corrosive place where it
will not be subjected to shocks or vibrations. When this is not possible,
assemble it inside a switchboard with a suitable degree of protection.
For preparation of the installation ambient, refer to the “Overall dimen-
sions” chapter, which provides information about the following points:
– minimum installation volumes of the circuit-breakers and derived
versions
– clearances to be respected for circuit-breakers in compartments
– overall dimensions of the circuit-breakers
– drilling holes for fixing purposes
– drilling holes in the compartment door
The operations required for installation, putting into service, routine and
supplementary maintenance must be performed by skilled personnel
with detailed knowledge of the equipment.
To install a circuit-breaker in the switchboard, just fix it to a vertical
surface with M8 screws. (fig. 7 )
The circuit-breaker must only be installed in a vertical position.
Fig. 6
Comply with the following instructions when lifting the circuit-breaker: the circuit-breakers must be placed on a sturdy surface and preferably lifted
with an appropriate fork-lift truck. The use of ropes is, however, permitted: In this case, the lifting ropes ust be attached as shown in the figure.
Circuit-breaker 3 poles 4 poles
kg lbs kg lbs
T8 2000
73
161 95 209
T8 2500
73
161
95
209
T8 3000
95
209
125
276