Mov - ac input only – Rockwell Automation 20B PowerFlex 700 Drive - Frame 7 Components Replacement User Manual
Page 54

54
Rockwell Automation Publication 20B-IN017B-EN-P - September 2011
Chapter 3 Component Replacement Procedures
MOV - AC Input Only
Refer to the figures in
Component Diagrams and Torque Specs on page 13
these instructions.
Remove Components
1. Read and follow the
and
.
2. Locate the MOV assembly.
Remove Precharge Board Assembly on page 23
4. Note wire placement and connections. Disconnect the MOV ground
wire and its R, S, and T wires at the top nut on the input power terminal
block.
5. Unscrew MOV mounting brackets.
6. Remove the MOV assembly.
Install Components
1. Install the new MOV assembly. Tighten the MOV mounting screw to
2.9 N•m (26 lb•in)
2. Reconnect all wires and connectors for the MOV.
3. Torque the R, S, and T Phase power terminal block nuts to 9.8 N•m (80
lb•in)
4. Reinstall the Precharge Board.
5. Replace all safety shields and enclosure covers before applying power to
the drive.