Rockwell Automation 63-xx PHOTOSWITCH Solid State Plug-In Logic Outputs User Manual

Installation instructions photoswitch, Solid state plug in logic outputs

Advertising
background image

INSTALLATION INSTRUCTIONS

PHOTOSWITCH

R

SOLID STATE PLUG IN LOGIC OUTPUTS

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. REPLACEMENT PARTS FOR BASES MANUFACTURED AND SOLD BEFORE 1991.

BULLETIN NUMBER

TYPE

VOLTAGE SUPPLY

CURRENT RATING

RESPONSE TIME

63--64

or

63--66

DC Voltage

Output Adapter

24 VDC

30 mA

Depends upon

Control Used

12 VDC

15 mA

63--65

or

63--67

Open Collector

Logic Output

24 VDC

250 mA

15 VDC

150 mA

12 VDC

125 mA

63- 64 or 63- 66

SPECIFICATIONS

No Load

20 VDC

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Load Resistance

Not less than 550 Ohms

. . . . . . . . . . . . . . . . . . . .

Ambient Temperature Range

--20°F to 135°F (--28°C to 57°C)

. .

Relative Humidity

95%

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Note: 63--66 and 63--67 Outputs supersede the 63--64 and 63--65 Out-

puts respectively. The new plug-in Outputs are electrically and
physically interchangeable with the old, but with the following
minor exceptions.

1.

The plastic cover on the 63--66 and 63--67 have curved domes
to match the curved spring retainers supplied on all Control
Bases with date code 8000 and higher.

2.

For Series 60--1400 and 60--1600 Control Bases manufactured
and installed prior to January 1980, which included the flat-top
spring retainer, order the 63--66 plus a 63--71 flat--top Adapter
for compatible Control Base mounting.

63- 65 or 63- 67

SPECIFICATIONS

Open Collector Rating as Current Sink

250mA for Vce = .25

. .

Ambient Temperature Range

--20°F to 135°F (--28°C to 57°C)

. .

Relative Humidity

95%

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Reverse Voltage Protection

Shunt Diode

. . . . . . . . . . . . . . . . . . . .

3.

When these Logic Adapters are used with Model 4003 Versions
of Type 42RL Controls, only DC input power should be ap-
plied. The user must also be certain to add a jumper between
control terminals L2 and 2C. This ties the negative power sup-
ply line terminal to the negative of the output circuit. In placing
this jumper and in connecting the power supply leads, the cor-
rect polarity must be observed to avoid internal damage.