Step 3: remove the control circuit board, Remove the control circuit board – Rockwell Automation 23P PowerFlex DC Stand-Alone Regulator (SAR) In-Rush Limiting Resistor User Manual

Page 4

Advertising
background image

4

Rockwell Automation Publication 23P-IN008A-EN-P - June 2011

Step 3: Remove the
Control Circuit
Board

1. Label and disconnect the ribbon cables at connectors XA, XR, and XFCD.
2. Unplug the terminal block connectors (6) from the control board (if wired).
3. Remove the EMI shield mounting screws (5), and save for reassembly.
4. Remove the EMI shield ground screw (1), and save for reassembly.

Note: The control board remains mounted to the EMI shield.

5. Carefully lift the EMI shield and control board (to provide clearance from cabling

below), and slide the EMI shield and control board out of the chassis, and carefully set
aside.

EMI Shield Mounting
Screws (5)
Tightening torque:
1.0 N•m (8.9 lb•in)

Terminal Block
Connectors (6)

XA

XR

XFCD

EMI Ground Screw (1)
Tightening torque:
1.0 N•m (8.9 lb•in)

Advertising