A.1 PLC Read Registers - Output from Drive

Register (ID)

Name

Type

Range

2048

Logic Status Word

Binary

Binary defined (A.2)

2049

Reserved

Integer 16 bit

2050

Reserved

Integer 16 bit

2051

Output Frequency (Feedback)

Integer 16 bit

0..240.00 Hz

2052

Output Speed (Feedback)

Integer 16 bit

0..10000 RPM

2053

Output Current

Integer 16 bit

0..99.9 A

2054

Heat Sink Temperature

Integer 16 bit

0..120°C

2055

Motor Power

Integer 16 bit

0..99.99kW

2056

Output Voltage

Integer 16 bit

0..999.9 V

2057

Energy

Integer 16 bit

0..65535kWh

2058

Drive Error (same as D007)

Integer 16 bit

0..122

Note: All values are without sign. The Modbus values have there decimal point adjusted as
defined in the table and not as defined in the standard instruction manual.

A.2 Definition for the Logic Status Word

Bit 15 – 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Not used

Running at

Zero Speed

At Freq

Alarm

Faulted Running

+

Backward

Running

Ready


Detailed bit description:
Running at Zero Speed

Bit = 1 when speed is below 2% of max frequency

At Freq

Bit = 1 when output frequency reached frequency command.

Alarm

Bit = 1 when alarm is active

Faulted

Bit = 1 when drive has tripped on fault.

Running + Backward

Bit = 1 when running backwards

Running

Bit = 1 when running

Ready

Bit = 1 when ready and accepting frequency commands.


A.3 PLC Write Registers - Input to Drive

Register (ID)

Name

Type

Range

2000

Logic Control Word

Binary 16 bit Binary defined (A.4)

2001

Reserved

Binary 16 bit

2002

Frequency Command relative to P035

Integer 16 bit

0..100.00% Fmax

2003

Reserved for customer, not used in the drive

Integer 16 bit

2004

Reserved for customer, not used in the drive

Integer 16 bit

2005

Reserved for customer, not used in the drive

Integer 16 bit

2006

Reserved for customer, not used in the drive

Integer 16 bit

The first register 2000 is used for the “Logic Control Word” and the register 2002 for the
“Frequency (Speed) Command”. The following up 4 registers from 2003 to 2006 are especially
reserved for the customer and are not used in the drives but external.