Rockwell Automation 20P PowerFlex DC Drive - Frame A Pulse Transformer Circuit Board User Manual
Page 17

PowerFlex® DC Drive - Frame A Pulse Transformer Circuit Board
17
Pulse Transformer Board FIR1-XX Rev. “Q” and Higher
Set DIP switches S3 and S4, located on the Pulse Transformer board (see
for location), to the correct settings based on the
appropriate table below.
Important: A blank cell below a switch in Tables E and F below indicate
that the setting is “OFF”.
Table E 230V AC Input Drives
Table F 460V AC Input Drives
Drive
Current
Rating
Code
DC
Amps
AC
Line
Amps HP
DIP Switch S3
DIP Switch S4
S3-1
S3-2
S3-3
S3-4
S3-5
S3-6
S3-7
S3-8
S4-1
S4-2
S4-3
S4-4
S4-5
S4-6
S4-7
S4-8
7P0
7
5.7
1.5
ON
ON
ON
9P0
9
7.4
2
ON
ON
ON
012
12
9.8
3
ON
ON
ON
020
20
16
5
ON
ON
ON
029
29
24
7.5
ON
ON
ON
038
38
31
10
ON
ON
055
55
45
15
ON
ON
ON
ON
073
73
60
20
ON
ON
ON
ON
093
93
76
25
ON
ON
ON
ON
110
110
90
30
ON
ON
ON
ON
Drive
Current
Rating
Code
DC
Amps
AC
Line
Amps HP
DIP Switch S3
DIP Switch S4
S3-1
S3-2
S3-3
S3-4
S3-5
S3-6
S3-7
S3-8
S4-1
S4-2
S4-3
S4-4
S4-5
S4-6
S4-7
S4-8
4P1
4.1
3.3
2
ON
ON
ON
6P0
6
4.9
3
ON
ON
ON
010
10
8.2
5
ON
ON
ON
014
14
11.4
7.5
ON
ON
ON
019
19
15.5
10 ON
ON
ON
027
27
22.1
15
ON
ON
ON
035
35
28.6
20
ON
ON
ON
045
45
36.8
25
ON
ON
ON
ON
052
52
42.5
30
ON
ON
ON
ON
073
73
59.6
40
ON
ON
ON
ON
086
86
70.3
50
ON
ON
ON
100
100
81.7
60
ON
ON
ON
ON
129
129
105.4 75
ON
ON
ON
ON