Table 1: Level and Resistance Control
Specifications
Power Consumption:
3 watts (includes control base)
Resistivity Range:
Typical liquid resistivity 0--60 MegOhms • centimeter
(See Table 5)
Resistance Sensing Sensitivity:
0--15 MegOhms in six ranges. (See Table 6, Consult factory for higher ranges.)
Maximum Probe Voltage:
22.5V AC (Ranges 1, 2, & 3), 29 VAC (Ranges 4, 5, & 6) (See Table 6)
Maximum Probe Current:
65 mA to 0.001 mA. (See Table 6)
Solid State Output Signal:
12V DC open circuit limited to 30mA short circuit. Terminals #5 and #2 on Control Base.
Speed of Response:
0.003 sec. to 0.20 sec. (See Table 7)
Permissible Lead Length:
Up to 2,000 ft (609.6 m) (See Table 8) Use #16 AWG wire minimum
Ambient Temperature:
--40 to 135°F (--40 to 57°C)
Bulletin Number
Control Base
Output
Voltage Supply
Output Characteristics
Response Time
Resistivity Range
Type
Rating
Leakage
13DJ3-3000
—
—
—
Refer to Table 7
Refer to Table 6
60-1600B
120V AC
50/60 Hz
—
—
—
60-1601B
240V AC
50/60 Hz
—
—
—
8-670
supplied with
control base
DPDT
EM
Relay
5A, 120V AC
2.5A, 240V AC
1A, 120V DC
—
8-651
SPNO
TRIAC AC
1A, 265V AC
20mA min.
1mA
8-652
SPNO
FET AC/DC
30mA,
120V AC/DC
10μA
63-116
Voltage
DC Output
30mA,
24V DC
—
63-115
NPN Open
Collector
250mA,
24V DC
1mA