Power wiring, I/o wiring recommendations, I/o terminal block specifications – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual

Page 4: English-4

Advertising
background image

English-4

Power Terminal Block (A Frame Shown)

Power Terminal Block Specifications

Input Power Conditions

I/O Terminal Block Specifications

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection

Circuit Breakers Application Ratings

.

(3)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/
277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(4)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or
non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations
may require a larger enclosure.

Power Wiring

Power Wire Rating

Recommended Copper Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Belden 29501-29507 or equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Shawflex 2ACD/3ACD or equivalent

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

Terminal

Description

R/L1, S/L2

1-Phase Input

R/L1, S/L2, T/L3

3-Phase Input

U/T1

To Motor U/T1

=

Switch any two motor leads to
change forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

BR+, BR-

Dynamic Brake Resistor Connection [0.75 kW (1 HP) ratings and higher]

Safety Ground - PE

Frame

Maximum Wire Size

(1)

Minimum Wire Size

(1)

Torque

A

3.3 mm

2

(12 AWG)

0.8 mm

2

(18 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

B

5.3 mm

2

(10 AWG)

1.3 mm

2

(16 AWG)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(2)

or Isolation Transformer

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Line has frequent power interruptions

Line has intermittent noise spikes in excess of 6000V (lightning)

Phase to ground voltage exceeds 125% of normal line to line voltage

Remove MOV jumper to ground.

or Install Isolation Transformer with
grounded secondary if necessary.

Ungrounded Distribution System

(2)

Refer to Appendix B of the PowerFlex 4 User Manual for accessory ordering information.

I/O Wiring Recommendations

(3)

Wire Type(s)

Description

Minimum Insulation Rating

Belden 8760/9460
(or equiv.)

0.8 mm

2

(18AWG), twisted pair, 100% shield with

drain.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

2

(18AWG), 3 conductor, shielded for

remote pot only.

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be
necessary, but is always recommended.

Maximum Wire Size

(4)

Minimum Wire Size

(4)

Torque

1.3 mm

2

(16 AWG)

0.13 mm

2

(26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)

(4)

Maximum / minimum that the terminal block will accept - these are not recommendations.