2sensor indicators, Mounting the sensor, Wiring diagrams – Rockwell Automation 42JS VisiSight Photoelectric Sensors User Manual

Page 2

Advertising
background image

2

Sensor Indicators

Green LED

Yellow Output

LED

Sensitivity

Adjustment

Knob

min

max

LED Status

Green

OFF

Power is Off

ON

Power is On

Flashing (6 Hz)

Unstable ( 0.5 < Margin < 2)

Flashing (1.5 Hz)

Output short-circuit protection active

Yellow

OFF

Output de-energized 

ON

Output energized 

Black wire or pin 4 of connector.

Sensor Alignment
1. Ensure that the sensitivity knob is set at its maximum

(factory default) setting.

2. Pan the sensor left, right, up and down to center the beam

on the sensed object (for diffuse), reflector (for

retroreflective) or transmitter (for transmitted beam). Fix the

sensor position when the green LED is ON (not flashing)

and the yellow output LED is ON (light sensed and L.O.

output energized). This set up assures a good margin and

that signal received is greater than twice the signal

required to energize the L.O output.

3.

a. For diffuse applications, remove the object being sensed

and observe the green LED. If the green LED is flashing

(at 6 Hz), it indicates that sensor is receiving more than

half the signal required to energize the L.O. output when

there should be minimal or no received signal. It

indicates that the sensor is getting close to detection of

background. Stability may be optimized by reducing the

reflectivity of the background or reducing the sensitivity.

Reducing the sensitivity shortens the sensing range. If

sensitivity is reduced, check that both the green and

yellow LEDs are on when the object is detected (step 2

above). In applications where full range is needed, i.e.,

sensitivity cannot be reduced, the green LED may be

left flashing.

b. For retroreflective and transmitted beam applications,

place the object to be sensed in the beam path and

observe the green LED. If the green LED is flashing (at

6 Hz), it indicates that sensor is receiving more than half

the signal required to energize the L.O. output when

there should be minimal or no received signal. It

indicates that the object being detected is letting some

light go through (semi-transparent or too small in size).

Adjust sensitivity and repeat step 2.

Crosstalk Avoidance
For applications of transmitted beam sensors requiring

adjacent pairs to be mounted in close proximity, use red LED

and infrared LED pairs as adjacent pairs.
The following spacing (center to center) between the adjacent

pairs should be maintained to avoid crosstalk:
1. Red LED pair adjacent to infrared LED pair:

a. 60 mm (2.4 in.) for sensing range up to 1.6 m (4.8 ft)
b. 20 mm (0.8 in.) for sensing range greater than 1.6 m

(4.8 ft)

2. Two adjacent pairs of red LED models or two adjacent

pairs of infrared LED: 360 mm (14 in.)

Four pairs can be mounted within the same spacing by

alternating the transmitter/receiver position.

Mounting the Sensor

Securely mount the sensor on a firm, stable surface or

support. A mounting which is subject to excessive vibration or

shifting may cause intermittent operation. Adaptors and

mounting brackets are available for a flexible installation. See

Accessories section for more details.

Wiring Diagrams

Cable connection is shown in the following diagrams. Pin

numbers correspond to an M12 or M8 male connector on the

sensor.

PNP Models with Complementary Outputs

Brown (1)

White (2)

Black (4)

Blue (3)

Load
Load

+

LO
DO

NPN Models with Complementary Outputs

4

3

1

2

3

2

1

4

Brown (1)
White (2)

DO

Black (4)
Blue (3)

Load
Load

+

LO

M12 Male

M8 Male

PNP Diagnostic Models

Light Operate

Dark Operate

Brown (1)
White (2)
Black (4)
Blue (3)

Load

+

LO

Diag

Brown (1)
White (2)
Black (4)
Blue (3)

Load

+

DO

Diag

NPN Diagnostic Models

Light Operate

Dark Operate

Transmitted Beam Emitter

Brown (1)
White (2)

Diag

Black (4)
Blue (3)

Load

+

LO

Brown (1)
White (2)

Diag

Black (4)
Blue (3)

Load

+

DO

Brown (1)

Black (4)

Blue (3)

+

Diagnostic output is energized if the sensor operation is unstable.

For normal operation, black wire (pin 4) needs no connection. To disable light source, connect

black wire (pin 4) to +V.

Advertising